NZH

Room hygrostat, single-stage

Application
The NZH is a room hygrostat for controlling and monitoring the relative humidity in offices and living rooms, bathrooms, laboratories, switch cabinets, IT rooms, etc., not suitable for aggressive gases.

Technical Data

Contact voltage:24... 230V AC,
> 24 V only in dry rooms according to VDE 0110
Adjustable range:35...100% r.H.
Switching capacity:dehumidify, 5 (0.2) A, min. 100 mA (contact load) humidify, 3 (0.2) A, min. 100 mA
Contact:dust-encapsulated microswitch as single-pin potential-free changeover switch (one/two), (Changeover contact)
Sensor element:Plastic fibres
Tolerance:max. 3 % r.H.
Switching differential:approx. 4% r.H.
Housing:Plastic, material ABS, colour pure white (Similar to RAL 9010)
Dimensions:115 x 70 x 35 mm
Housing temperature:+5°C...+60°C
Electrical connection:0,14 - 2,5 mm² via screw terminals on circuit board
Protection class:II (according to EN 60 730)
Protection type:IP 30 (according to IEC 529)
Function:
Humidifiy:Wire contacts 1 and 2. The switching points ON/OFF are approx. 2 % r.h. above and below the selected value.
Dehumidify:Wire contacts 1 and 4. The switching points ON/OFF are approx. 2 % r.h. above and below the selected value.