RPTF RS485
Pendulum room temperature sensor with RS485 output
Application
The RPTF RS485 is a pendulum temperature sensor with remote electronics housing IP65 with quick-release screws. The signal of which communicates via RS485 Modbus®-RTU and S-Bus. For recording the temperature especially in larger rooms and halls. The RPTF RS485 (globe thermometer) determines the effective radiant component or also the effective radiant heat at the measuring point.
Technical Data
Measuring range: | -0...+50°C |
Power supply: | 24V DC ± 20 % |
Power consumption idle: | 15mA |
Bus protocol: | RS485 Modbus®-RTU / S-Bus |
Configuration option: | via Dip switches (address number, parity, baud) |
Address number: | 1 to 63 (0 not allowed) |
Parity mode for Modbus: | no parity, even parity, odd parity |
Saia S-Bus: | Data Mode |
Transmission rate: | 4800, 9600, 19200, 38400 Baud |
Inputs: | PT1000 1/3 DIN (24 bit resolution / 0.1 °C) |
Ambient temperature: | -30°C...+60°C |
Storage temperature: | -40°C...+70°C |
Accuracy: | <<0.1% for temperature measurement PT1000 |
Temperature coefficient: | <0.003% / K for temperature measurement PT1000 |
Connection head: | Plastic, polyamide, 30% glass-ball reinforced, with quick-release screws, colour pure white (similar to RAL9010) |
Dimensions: | 70 x 62 x 37mm |
Sensor cable: | 2m PVC; LiYY 2x0.25mm² (other lengths optional) |
Protective pipe: | Stainless steel, 1.4571, V4A Ø = 15mm, nominal length NL=100mm |
Electrical connection: | up to 2.5 mm² via double push-in terminals |
Cable gland: | 2 x M16, with strain relief |
Humidity: | < 95 % rH, non-condensing air |
Protection class: | III (according to EN 60 730) |
Protection type: | IP65 (acc. to IEC 529) |
Standards: | CE conformity EMC guidelines: according to EN55011 class B |
RPTF RS485