MU HS-x PT100/PT1000

transducer PT100/PT1000 for standard rail 35mm

Application
The digital transducer is used to convert the passive sensor PT1000/PT100 to standard signals 4… 20mA or 0-10V. The different PT sensors are automatically recognised.

transducer with output 0…10V

Measuring range:adjustable with Dip switch, see table
Connection:3-wire connection
Power supply voltage:24V AC/DC ±20%
EMC:according to EN 61326
Measuring element:PT100/PT1000
(detected by the transducer itself)
Operating temperature:-20...+60 °C non-condensing
Accuracy:< 0,1%
Max. Output current:2mA
Temperature coefficient:< 0,003% / K
Housing:Plastic
Dimensions WxHxD:17,5 x 90 x 55 mm
Protection type:IP21

transducer with output 4…20mA

Measuring range:adjustable with Dip switch see table
Connection:2-wire connection
Supply voltage:15...30V DC, supply from 4...20mA loop
EMC::according to EN 61326
Measuring element:PT100/PT1000
(detected by the transducer itself)
Operating temperature:-20...+60 °C non-condensing
Humidity:< 95 % rH, non-condensing air
Accuracy:< 0.1 %
Load resistance:< 550 Ω
Temperature coefficient:< 0.003% / K
Housing::Plastic
ADimensions WxHxD:17,5 x 90 x 55 mm
Mounting:on standard rail
Protection type:IP21

MU-HS-U

MU-HS-I