KTF 1 RS485 incl. mounting flange
Duct temperature sensor/Air duct sensor with RS485 output
Application
The KTF 1 RS485 is a duct temperature sensor in IP65 housing with quickrelease screws, whose signal communicates via RS485 Modbus®-RTU and S-Bus. For detecting the temperature of gases, e.g. in ventilation and air conditioning ducts.
Technical Data
Measuring range: | -50..+150°C |
Power supply: | 24V DC ± 20 % |
Power consumption idle: | 15mA |
Bus protocol: | RS485 Modbus®-RTU / S-Bus |
Configuration option: | via Dip switches (address number, parity, baud) |
Address number: | 1 to 63 (0 not allowed) |
Parity mode for Modbus: | no parity, even parity, odd parity |
Saia S-Bus: | Data Mode |
Transmission rate: | 4800, 9600, 19200, 38400 Baud |
Inputs: | PT1000 1/3 DIN (24 bit resolution / 0.1 °C ) |
Ambient temperature: | -30°C...+60°C |
Storage temperature: | -40°C...+70°C |
Accuracy:: | <<0.1% for temperature measurement PT1000 |
Temperature coefficient: | <0.003% / K for temperature measurement
PT1000 |
Protective pipe: | Stainless steel, 1.4571, V4A, Ø = 6mm |
Connection head: | Plastic, polyamide, 30% glass-ball reinforced, with quick-release screws, colour pure white (similar to RAL9010) |
Dimensions:: | 70 x 62 x 37mm |
Cable gland: | 2 x M16, with strain relief |
Electrical connection: | up to 2.5 mm² via double push-in terminals |
Process connection: | by means of flange, galvanised steel (included) |
Insulation resistance: | ≥ 100 MΩ at 20 °C (500V DC) |
Humidity: | < 95 % rH, non-condensing air |
Protection class: | III (according to EN 60 730) |
Protection type: | IP 65 (according to IEC 529) |
Standards:: | CE conformity |
EMC guidelines: | according to EN55011 class B |