DFL

Pressure and differential pressure transducer, with active output and 8 switchable measuring ranges

Application
The DFL is a differential pressure transducer and is used to measure overpressure, underpressure or differential pressure in the air. The digital sensor (MEMS) guarantees high reliability and accuracy. These pressure sensors are used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray cabins, in commercial kitchens, for purposes of filter monitoring and fill level measurement or to control frequency inverters. The measured medium is air (non-condensing) or gaseous, non-aggressive, non-combustible media.

Technical Data

Power supply:24V AC/DC with output 0-10V 15-30V DC with output 4...20mA
Output signal:0-10V oder 4...20mA
Measuring range:8 adjustable measuring ranges (see table)
Media temperature:-20...+50°C
Circuit type:2- or 3-wire connection
Pressure connector:4/6 x 11mm (hose Ø = 4/6mm)
Type of pressure:Differential pressure
Medium:Air, non-aggressive, non-combustible gases
Long-term stability:±1,5% per year
Rise time:approx. 0,05s
Hysteresis:0.1% of input value, ranges 25, 50, 100Pa: 1 Pa parts in contact with the medium: MS, Ni, Nylon, PU, Si
Temp. drift values:±2,5% input value
Power consumption:< 20mA
Linearity:±0,8% input value
Connection head:Plastic, polyamide, 30% glassball-reinforced, with quick-release screws, colour pure white (similar to RAL 9010)
Dimensions:70 x 62 x 37 mm
Electrical connection:0,14 - 1,5 mm² via screw terminals
Cable gland:M16, with tension relief
Humidity:< 95 % r. H., non-condensing air
Protection class:III (according to EN 60 730), Protection type: IP 65 (according to IEC 529)
Standards:CE conformity, electromagnetic compatibility tolerance according to EN 61 326 +A1+A2 EMV Directive 89/336/EWG

DFL