VF S15 Premium
Toshiba frequency inverter
Application
The VF-S15 is a frequency inverter (rated motor power from 0.25kW – 18.5kW) for stepless speed control of asynchronous and PM motors. Use in mechanical engineering, materials handling, industrial applications, lift, lifting and crane applications. Diverse integration variants through various Fieldbus connections, Modbus RTU, Toshiba RS-485 as standard.
Technical Data
Mains connection: | 1 x 200-240V ±10%, 50/60 Hz ±5% 3 x 380-500V ±10%, 50/60 Hz ±5% |
Control method: | Pulse-width modulated sine waveform (PWM) |
Rated output voltage: | VFS15SxxxPL(-W) 50 - 300V VFS15xxxPL(-W) 50 - 660V (max. Mains voltage) |
Output frequency: | 0.1..500Hz |
Current in case of overload: | 150% (120% with M=square characteristic curve) for 60 s, 200% for 0.5 s |
Control inputs digital: | 6(8)³ positive / negative logic switchable, Control voltage 24 V DC int/ext, pulse input 10...20 kpps, permanently assigned: 1 x STO (not with VF-S15PL-W) |
Control inputs analogue: | 3(1)³, VIA: 0...10V, VIB: - 10(0)...+10V, VIC: (0)4...20mA |
Control outputs: | 2 relay outputs, 1 potential-free digitalor pulse output 10...20 kpps, 1 analogueoutput 0...10V or 4(0) ....20mA |
Brakes: | Brake chopper integrated, external Braking resistor connectable |
Interfaces internal: | Modbus®-RTU, Toshiba RS-485 |
Interfaces optional: | PROFIBUS®DP, CANopen®, Profinet® (in Preparation) , EtherNet/IP®, EtherCAT®, Modbus®TCP, unitNet®, CC-LINK |
Protective functions: | PTC evaluation, overtorque, Undercurrent, overcurrent, overload, overtemperature, phase failure, earth fault, Winding short circuit etc |
Integrated EMC filter: | 1-phase 240V, 3ph. 500V EMC filter (IEC61800-3 category C2) |
Ambient temperature: | 10 to +60°C |
Humidity: | < 95 % rH, non-condensing air |
Protection type: | IP 20 |

VF S15