FB …

 Fieldbus unit as replacement for Messner (Vario-Miles)

Application
 The FB…is a Fieldbus module for setting up distributed systems (Fieldbus systems) in industry, building services and HVAC. These units can be arranged in a centralised and decentralised way and can be read and written by a central CPU (PLC, PC) or with a Hakko touch panel via interface RS485 and Modbus®-RTU. Depending on the application, various digital and analogue inputs and outputs are used.

Technical Data

Power supply voltage:24V DC ±20%
No-load current:20mA
max. current draw:see table
Bus protocol:RS485, Modbus®-RTU
Digital input:24V DC, 5mA
Analogue input:XI configurable as:
PT100/1000: MB: -100...+500 °C, resolution
0.1 °C, NI1000, NI1000 TK5000, T1S and
resistance, 0...10V (resolution 1mV)
LM235Z, LM135Z, NTC10kOhm
Digital output:HL 60V / 80mA
Output analogue:0...10V (resolution 1mV)
Ambient temperature:0...+50°C
Accuracy:< 0.1 %
Analogue resolution:0.1°C
EMC:according to EN 61326
Terminals:Plug-in terminals with push-in connection up
to 2.5mm²
Housing dimensions:45mm in-line installation system HxWxD:
108x133x43 mm
Installation:TS35 profile rail
Humidity:< 95 % rH, non-condensing air
Protection type:IP006
Standards:CE conformity