TWA U/W continuous
Continuous dew point monitor with output 0…10V and changeover contact
Application
The TWA U/W is a humidity sensor with a remote sensor. It is mounted on cooling/cold water pipes or on cool surfaces. It can be used as a humidity sensor, dew point monitor or limit switch on pipes to prevent condensation on pipes. Installation is possible both on metal pipes and optionally with heat conductive paste on plastic pipes is possible.
The dew point temperature is the temperature at which the air reaches saturation and water begins to condense. Unit and line interruptions are signalled at the same time
Technical Data
Power supply: | 24V DC/AC ± 20% |
Power consumption: | 10mA |
Output signal: | analogue 0-10V, 0V = 100% or inverted additional potential-free changeover contact Contact load up to 30V / 1A (relay is energised at low humidity) |
humidity sensor: | MB: 0 ... 100%, error at 100%, typically 3.5% MB: 20 ... 80%, error typical 2% |
Connection head: | PP GF30 + aluminium, protection class IP50 |
Dimensions: | 9x10x60mm |
Cable length: | Standard 200mm, option up to 1000mm |
Process connection: | Cable tie, 180 mm, for pipes up to 3" (included) when mounting on plastic pipes, a heat-conducting paste is necessary |
Housing: | Plastic, polyamide, 30% glass-ball reinforced, with quick-release screws, colour pure white (similar to RAL9 |
Dimensions: | 70 x 62 x 37mm |
Cable gland: | M16, with tension relief |
Ambient temperature: | -30°C...+60°C |
Humidity: | < 95 % rH, non-condensing air |
Electrical connection: | Screw terminals 0.14 - 1.5mm² |
Protection class: | Screw terminals 0.14 - 1.5mm² |
Protection type: | IP63 |
TWA U/W