TWA U/W continuous

Continuous dew point monitor with output 0…10V and changeover contact

Application

The TWA U/W is a humidity sensor with a remote sensor. It is mounted on cooling/cold water pipes or on cool surfaces. It can be used as a humidity sensor, dew point monitor or limit switch on pipes to prevent condensation on pipes. Installation is possible both on metal pipes and optionally with heat conductive paste on plastic pipes is possible.

The dew point temperature is the temperature at which the air reaches saturation and water begins to condense. Unit and line interruptions are signalled at the same time

Technical Data

Power supply:24V DC/AC ± 20%
Power consumption:10mA
Output signal:analogue 0-10V, 0V = 100% or inverted
additional potential-free changeover contact
Contact load up to 30V / 1A
(relay is energised at low humidity)
humidity sensor:MB: 0 ... 100%, error at 100%, typically 3.5% MB:
20 ... 80%, error typical 2%
Connection head:PP GF30 + aluminium, protection class IP50
Dimensions:9x10x60mm
Cable length:Standard 200mm, option up to 1000mm
Process connection:Cable tie, 180 mm, for pipes up to 3" (included)
when mounting on plastic pipes,
a heat-conducting paste is necessary
Housing:Plastic, polyamide, 30%
glass-ball reinforced, with quick-release
screws, colour pure white (similar to RAL9
Dimensions:70 x 62 x 37mm
Cable gland:M16, with tension relief
Ambient temperature:-30°C...+60°C
Humidity:< 95 % rH, non-condensing air
Electrical connection:Screw terminals 0.14 - 1.5mm²
Protection class:Screw terminals 0.14 - 1.5mm²
Protection type:IP63