RCO2.T.RH.x RS485 – RLQ.T.RH RS485
Multifunction room bus unit CO2 and/or air quality sensor RS485
Application
The RCO2.T.RH.x RS485 or RLQ.T.RH RS485 multifunction room bus unit – whose signal communicates via RS485 and by means of Modbus®-RTU / S-Bus, records the CO2 content and the temperature and/or the air quality and the relative and absolute humidity in the room air, depending on the variant of the unit.
Technical Data
Power supply: | 24V DC ± 10 % |
Power consumption: | RCO2+T 12mA (max. 60mA) RCO2+T+LQ 23mA (max. 80mA) RCO2+T+RH 12mA (max. 60mA) RCO2+T+RH+LQ 23mA (max. 80mA) RLQ+T / RLQ+T+RH 18mA |
Bus protocol: | RS485 Modbus RTU / S-Bus (incl. BUS LED red/green) |
Configuration option: | via Dip switches (address number, parity, baud) |
Address number: | 1 to 63 (0 not allowed) |
Parity mode for Modbus: | no parity, even parity, odd parity |
Transmission rate: | 4800, 9600, 19200, 38400 Baud |
CO2: | MB: 0...5000 ppm, resolution 1 ppm, measuring error ±30 ppm |
Temperature: | MB: 0...+50 °C, resolution 0.1 °C, measuring error ± 0.3 °C |
Air quality: | 1 LSB / 0...1000 0 LSB clean air 1000 LSB bad air |
Relative humidity: | MB: 0...+100%, resolution 1%, Measuring error at 20...80%, ± 3 |
Absolute humidity: | 0,1gr/m³ |
Operating temperature: | 0°C...+50°C |
Storage temperature: | -20°C...+80°C |
Humidity: | < 95 % rH, non-condensing air |
Terminals: | Screw terminals 0.14 - 1 mm² (acc. to VDE) |
Housing: | Plastic, material ABS, Colour pure white (similar to RAL 9016) |
Dimensions: | W x H x D 105 x 80 x 23.5 mm |
Mounting: | on flush-mounted box, Ø 55mm |
EMC guidelines: | according to EN55011 class B |
Standards: | CE conformity |
Protection type: | IP30 |
RCO2.T.RH.LQ RS485