NEW! RBG LEONIS Master-Slave RS485 (3,5”IPS Touch)

Modbus®-RTU, with frameless glass front and capacitive touch Aluminium frame black anodised or painted in white

Application

Leonis-3.5 is a room operating unit with two RS485 interfaces, one USB and one interface.
Up to ten screens can be programmed/configured.

Standard configuration with humidity and temperature sensor (optional CO²)
Basic I/O configuration: 2xDI, 1xAI-U, 2xAO-U, on customer request 1xPT1000, 2xOC
Application for visualisation and autonomous operating, control and regulation tasks.
e.g.: individual room control, ventilation control, light and blind control, etc.

Technical Data

Supply voltage:                 24V DC +10%, – 10%
Power:                                 approx. 0.2 W
Version:                               Temperature and humidity (RH/AH), optional CO2
Display type:                       3.5” RGB IPS TFT
Resolution:                          320 x 480 pixels
Processor:                            32 Bit, 2M Flash, 640k RAM
Additional:                           Real-time clock, battery-buffered
                                               8M Flash for configuration
                                               64K EEPROM for configuration
                                               Bus system 1x Modbus RTU slave for communication in the network
                                               1x Modbus RTU master for controlling the I/Os
                                               1x interface port for UP I/Os, Wifi, NT
                                               1x micro USB for software and configuration update
Inputs:                                  2DI 24V / 5mA (internal pull-up -> negative logic)
                                               1AI-U (0-10V)
Outputs:                               2AO-U (0-10V)
Function icons:                   Icons freely positionable
Display:                                Actual value, setpoint, temperature, humidity, date, time and customised values
Terminating resistors:      can be activated with a jumper
Parameter setting:             via the configuration menu
Baud rate:                            adjustable up to 115200 baud
Ambient temperature:     0…+50°C
Humidity:                            < 80% rH, non-condensing air
Connection:                         plug-in double push-in terminals for RS485 and 24V,
                                              plug-in single push-in terminals for I/Os
Mounting:                            using stainless steel plate on flush-mounted box diam. 55mm or
                                                Surface-mounted with surface-mounted frame and stainless steel plate
                                                Fixing with grub screw at the bottom
Dimensions WxHxD:         80 x 100 x 12 mm CO2 version 16.5 mm, mounting compatible with Leonis
Protection class:                 IP30