KCO2.T.RH.x RS485 – KLQ.T.RH RS485

Multifunctional Channel Bus Units RS485

Application
The KCO2.T.RH.x RS485 or KLQ.T.RH RS485 with or without display multifunctional channel bus unit whose signal communicates via RS485 and by means of Modbus®- RTU records the CO2 content, the temperature as well as the relative/absolute humidity and/or the quality of the air, depending on the version.

Technical Data

Power supply:24V DC ± 10%
Max. current draw:KCO2.T.RH 12mA (max. 60mA), KCO2.T.RH.LQ 23mA
(max. 80mA), KLQ.T.RH 18mA
Bus protocol:RS485 Modbus RTU
Configuration option:via Dip switches (address no., parity, baud)
Address number:1 to 63 (0 not allowed)
Parity mode for Modbus:no parity, even parity, odd parity
Transmission rate:4800, 9600, 19200, 38400 Baud
CO2:MB: 0...40000 ppm, resolution 1 ppm,
measuring error at auto calibration +-30 ppm +-3%
Auto calibration CO2:can be deactivated via jumper
Manual calibration CO2:by means of clean air and calibration button
Temperature:MB: -50...+100 °C, resolution 0.1 °C, meas. error ± 0.3°C
Air quality:1 LSB / 0...1000, 0 LSB clean air
1000 LSB bad air
Relative humidity MB:0...100%, resolution 1%,
Measuring error at 20...80%, ± 3
Absolute humidity:0,1 gr/m³
Ambient temperature:0...+50°C
Humidity:< 95 % rH, non-condensing air
Connection head:ABS/PC, pure white (similar to RAL9010),
4 quick release screws
Dimensions:81 x 55 x 35mm plus PGs
Protective pipe:ABS/ PC,
colour pure white (similar to RAL9010)
KCO2.T.RH+x: EL = 165mm, Ø 28.5mm
KLQ.T.RH: EL = 160mm, Ø 16mm
Display (optional):LCD display for T, rH,, CO2, VOC with
different display modes
Electrical connection:0.14 - 1.5 mm² via terminals on circuit board
Process connection:with mounting flange ABS/PC (included)
Cable gland:2 x M16, with strain relief
Protection class:III (according to EN 60 730)
Protection type:Housing IP 65,
Sensor IP40 (according to IEC 529)

KC02.T.RH.LQ RS485