ATF 2 RS485
Exterior/damp room temperature sensor with RS485 output
Application
The ATF 2 RS485 is an exterior temperature sensor in IP65 housing with quick-release screws and external stainless steel sensor tube. The signal of which communicates via RS485 Modbus®-RTU and S-Bus. For recording the exterior temperature in damp areas. Such as weather sensors for mounting on exterior walls, in cold storage and greenhouses, in halls, in the industrial sector and in agriculture. Exterior areas, installation is preferably on the north side or in a protected location. In direct sunlight, use the sunshade.
Technical Data
Measuring range: | - 50 ...+90 °C |
Power supply: | 24V DC ± 20% |
Power consumption idle: | 15mA |
Bus protocol: | RS485 Modbus®-RTU / S-Bus |
Configuration option: | via Dip switches (address number, parity, baud) |
Address number: | 1 to 63 (0 not allowed) |
Parity mode for Modbus: | no parity, even parity, odd parity |
Saia S-Bus: | Data Mode |
Transmission rate: | 4800, 9600, 19200, 38400 Baud |
Inputs: | PT1000 1/3 DIN (24 bit resolution / 0,1°C) |
Ambient temperature: | -30°C...+60°C |
Storage temperature: | -40°C...+70°C |
Accuracy: | < 0,1% for temperature measurement PT1000 |
Temperature coefficient: | < 0,003% / K for temperature measurement PT1000 |
Housing: | made of plastic, polyamide, 30% glass-ball reinforced, with quick-release screws, colour pure white (similar to RAL9010) |
Dimensions: | 70 x 62 x 37 mm |
Cable gland: | 1 oder 2 x M16 , with strain relief |
Electrical connection: | up to 2.5 mm² via double push-in terminals |
Insulation resistance: | ≥ 100 MΩ, at 20 °C (500V DC) |
Humidity: | < 95 % r. H., non-condensing air |
Protection class: | III (according to EN 60 730) |
Protection type: | IP 65 (according to IEC 529) |
Standards: | CE conformity |
EMC: | according to EN55011 class B |