DFL
Pressure and differential pressure transducer, with active output and 8 switchable measuring ranges
Application
The DFL is a differential pressure transducer and is used to measure overpressure, underpressure or differential pressure in the air. The digital sensor (MEMS) guarantees high reliability and accuracy. These pressure sensors are used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray cabins, in commercial kitchens, for purposes of filter monitoring and fill level measurement or to control frequency inverters. The measured medium is air (non-condensing) or gaseous, non-aggressive, non-combustible media.
Technical Data
Power supply: | 24V AC/DC with output 0-10V 15-30V DC with output 4...20mA |
Output signal: | 0-10V oder 4...20mA |
Measuring range: | 8 adjustable measuring ranges (see table) |
Media temperature: | -20...+50°C |
Circuit type: | 2- or 3-wire connection |
Pressure connector: | 4/6 x 11mm (hose Ø = 4/6mm) |
Type of pressure: | Differential pressure |
Medium: | Air, non-aggressive, non-combustible gases |
Long-term stability: | ±1,5% per year |
Rise time: | approx. 0,05s |
Hysteresis: | 0.1% of input value, ranges 25, 50, 100Pa: 1 Pa parts in contact with the medium: MS, Ni, Nylon, PU, Si |
Temp. drift values: | ±2,5% input value |
Power consumption: | < 20mA |
Linearity: | ±0,8% input value |
Connection head: | Plastic, polyamide, 30% glassball-reinforced, with quick-release screws, colour pure white (similar to RAL 9010) |
Dimensions: | 70 x 62 x 37 mm |
Electrical connection: | 0,14 - 1,5 mm² via screw terminals |
Cable gland: | M16, with tension relief |
Humidity: | < 95 % r. H., non-condensing air |
Protection class: | III (according to EN 60 730), Protection type: IP 65 (according to IEC 529) |
Standards: | CE conformity, electromagnetic compatibility tolerance according to EN 61 326 +A1+A2 EMV Directive 89/336/EWG |