RFTF RS485
Room humidity and temperature sensor with RS485
Application
The RFTF RS485 is a humidity/temperature sensor whose signal communicates via RS485 and by means of Modbus®-RTU / S-Bus and measures the relative, absolute humidity and temperature of the air, e.g. in refrigeration, air-conditioning and clean room technology, in living rooms, offices, hotels, technical rooms, assembly and conference rooms.
Technical Data
Power supply: | 24V DC ± 20% |
Power consumption idle: | 5mA |
Bus protocol: | RS485 Modbus®-RTU / S-Bus |
Configuration option: | via Dip switches (address number, parity, baud) |
Address number: | 1 to 63 (0 not allowed) |
Parity mode for Modbus: | no parity, even parity, odd parity |
Transmission rate: | 4800, 9600, 19200, 38400 Baud |
Temp. measuring range: | MB: 0...+50 °C, resolution 0.1 °C, measuring error ± 0.3 °C |
Measuring range relative humidity: | MB: 0...100% rH, working range 20...95% rH Resolution 1%, measuring error at 20...80% ±3 |
Measuring range absolute humidity: | 0,1 gr/m³ |
Ambient temperature: | 0°C...+50°C |
Humidity: | < 95 % rH, non-condensing air |
Housing: | Plastic, material ABS, colour pure white (similar to RAL9010) |
Dimensions: | 80 x 105 x 23.5 mm |
Installation: | Wall mounting or on flush-mounted box Ø 55mm, Bottom part with 4 holes, for mounting on vertically or horizontally installed Flush-mounted boxes |
Electrical connection: | 0.14 - 1 mm², via screw terminals |
Protection class: | III (according to EN 60730) |
Protection type: | IP30 (acc. to IEC 529) |
Standards: | CE conformity |
EMC guidelines: | according to EN55011 class B |